"status": "sensitivity-not-qualification",
"fan": "MF40200V1-1000U-G99",
"source": "https://www.sunon.com/PROSEARCH_FILES/%28D04114960G-01%29-1.pdf",
"sourceSha256": "d53ea62dda37fb564c627d3c7bc85fa07bd4890f4794a4c2ce5948aba8ab6fd4",
"sourcePages": [
4,
5
],
"rows": [
{
"grossDuctMm": [
40,
40
],
"rpm": 5000,
"targetLfm": 400,
"requiredCfm": 6.8889026666942215,
"nominalFreeAirCfm": 6.357142857142857,
"freeAirHeadroomCfm": -0.5317598095513647,
"canReachTargetEvenAtZeroPressureUnderAffinityApproximation": false
},
{
"grossDuctMm": [
40,
40
],
"rpm": 5950,
"targetLfm": 400,
"requiredCfm": 6.8889026666942215,
"nominalFreeAirCfm": 7.565,
"freeAirHeadroomCfm": 0.6760973333057789,
"canReachTargetEvenAtZeroPressureUnderAffinityApproximation": true
},
{
"grossDuctMm": [
40,
40
],
"rpm": 7000,
"targetLfm": 400,
"requiredCfm": 6.8889026666942215,
"nominalFreeAirCfm": 8.9,
"freeAirHeadroomCfm": 2.011097333305779,
"canReachTargetEvenAtZeroPressureUnderAffinityApproximation": true
},
{
"grossDuctMm": [
45.974,
31.75
],
"rpm": 5000,
"targetLfm": 400,
"requiredCfm": 6.2847222222222205,
"nominalFreeAirCfm": 6.357142857142857,
"freeAirHeadroomCfm": 0.07242063492063622,
"canReachTargetEvenAtZeroPressureUnderAffinityApproximation": true
},
{
"grossDuctMm": [
45.974,
31.75
],
"rpm": 5950,
"targetLfm": 400,
"requiredCfm": 6.2847222222222205,
"nominalFreeAirCfm": 7.565,
"freeAirHeadroomCfm": 1.2802777777777798,
"canReachTargetEvenAtZeroPressureUnderAffinityApproximation": true
},
{
"grossDuctMm": [
45.974,
31.75
],
"rpm": 7000,
"targetLfm": 400,
"requiredCfm": 6.2847222222222205,
"nominalFreeAirCfm": 8.9,
"freeAirHeadroomCfm": 2.61527777777778,
"canReachTargetEvenAtZeroPressureUnderAffinityApproximation": true
}
],
"limits": [
"Gross-duct velocity is not fin-channel velocity or guaranteed equivalence to the heatsink catalog test",
"Free-air flow and shutoff pressure are different operating points",
"RPM affinity scaling is an approximation; nominal published curve is not a minimum performance guarantee",
"Duct, guard, fin and recirculation pressure losses must be intersected with the fan curve",
"A turning fan and tach signal do not detect a blocked inlet; retain independent case-temperature protection",
"The 5000 RPM controller limit is a preliminary fault threshold, not an airflow qualification"
],
"next": "Specify duct and actual fin geometry, calculate pressure-loss curve, then verify installed airflow/temperature and low-RPM/fan-stall shutdown."
}