Temperature trip and measurement margin

The long-lead sensor is NTCLE428E3103H301A. Its nominal table conversion is now in the output-locked diagnostic firmware. This report was refreshed on 2026-10-13 by compiling and calling that actual C conversion, replacing the obsolete NTCLE100 curve used in the earlier sensitivity report. The sensor and installed attachment remain unqualified.

A reproducible static sensitivity check combines that table's resistance tolerance, the existing nominal firmware conversion, a 10 kΩ ±1% pull-up and ideal 12-bit ADC rounding:

Indicated cutoff Earliest sensor temperature Latest sensor temperature
55 C, raw-cutoff sensitivity only 53.77 C 56.26 C
54 C, sensitivity only 52.75 C 55.21 C
53 C, sensitivity only 51.76 C 54.20 C

These are log-resistance interpolations, not guaranteed extrema between tabulated points. They exclude ADC offset/gain/INL/noise, resistor drift, self-heating, attachment gradients and thermal lag. Even the 53 C illustration is not an approved threshold or complete error budget. The existing 55 C actual-case limit is unchanged.

Vishay lists an approximately 2.5-second response in oil, permits taped/glued mounting, and excludes hard potting. That response is not the installed case-sensor response or a justified RC time constant. Manufacturer sheet.

Before enabling load, qualify the exact sensor, attachment and acquisition chain against a reference case-temperature measurement across the intended range. Establish the maximum under-reading including transient lag, then derive an indicated cutoff that preserves the actual-case ceiling. Check the independent comparator separately; its nominal threshold is not a calibrated substitute for the software measurement. The bring-up image remains output locked.

Reproduce with python3 tools/sensor_trip_budget.py. Inputs · Results.

Implemented qualified upper-bound guard

The policy now compares case_c + case_margin_c with the unchanged 55 °C actual-case ceiling. The margin must be positive, finite and supplied by trusted assembly calibration with temperature_qualified=true. Unknown qualification prevents arming and faults a running core. Neither field can be set over the serial protocol. The allowance must cover under-reading, attachment gradients and qualified transient lag; the static table above cannot supply that allowance by itself.

No production margin has been selected. Host fixtures use an explicitly synthetic 2 °C allowance to exercise boundaries, not to qualify this assembly. The STM32 diagnostic adapter supplies unknown qualification and remains permanently output locked. Read-only telemetry reports the nominal estimate, margin and qualified upper bound; the panel refuses enable when the bound is unknown or reaches 55 °C.