Fan RPM and cooling airflow

The selected tach fan has a published nominal pressure/flow curve: Sunon MF40200V1-1000U-G99, drawing D04114960G-01, revision 17 May 2021, pages 4–5. It specifies 7000 RPM ±15%, 8.9 CFM free air and 0.22 inch-water shutoff pressure. These endpoints do not occur together. Manufacturer specification.

The existing 5000 RPM fault threshold does not establish the 400 LFM airflow assumed by the stock heatsink sensitivity calculation. An illustrative same-fan speed scaling gives 6.36 CFM free air at 5000 RPM. A 40 × 40 mm gross duct requires 6.89 CFM for 400 LFM, already above that zero-pressure estimate. A 45.974 × 31.75 mm gross section requires 6.28 CFM, leaving almost no pressure-loss allowance. These are geometry/affinity calculations, not installed-flow measurements or fin-channel velocities.

At nominal 7000 RPM, the published curve has useful pressure at those flows; at the specified low-speed tolerance the margin is smaller. A fan’s rated airflow alone cannot validate a heatsink’s catalog resistance. The duct, fin passages, guard and recirculation paths need a pressure-loss curve and installed operating-point verification. The firmware and control panel remain enable-locked pending assembly qualification. Do not simply raise the RPM threshold and declare cooling passed.

A blocked inlet can leave the rotor turning. Keep independent case-temperature shutdown as well as tach validity, speed limits and fault latching. Qualification must exercise low RPM, stalled rotor, blocked intake, disconnected tach, sensor failure and hot ambient with the actual interface and duct.

Reproducible envelope: python3 tools/fan_airflow_envelope.py. Nominal RPM affinity is an approximation and the published curve is not a guaranteed minimum performance bound.