MCR-SLP-1-5-UI-0

Phoenix ContactCURRENT TRANSDUCER

Loop-powered MCR passive current measuring transducer for sinusoidal alternating currents, 0 to 1 A AC or 0 to 5 A AC (reconnectable), converting to a 0 to 10 V or 0 to 20 mA output signal, without switching output. Screw connection, 22.5 mm wide on a 35 mm DIN rail.

Order no. 2814359Input 0..1 A / 0..5 A ACOutput 0..10 V / 0..20 mASize 22.5 x 99 x 114.5 mmMounting TS35 railGTIN 4017918148447
Schematic symbol by Adam Skotarczak. The symbol is MCR-SLP-1-5-UI-0_(U) from his realAscot/kicad-symlib, © 2025 Adam Skotarczak, ionivation.com, free to use, modify and redistribute with credit. It installs with the whole library from the Wolfgang's KiCad library (KiCad PCM repository), where this footprint and 3D model are linked to it.
Datasheet-built CAD: check before you rely on it. The 3D model is built from Phoenix Contact's published dimensions and front view, not from Phoenix Contact's own CAD, so its envelope is right but details are representative. The footprint's terminal positions and pitch are scaled from the front-view drawing and are approximate (plan for about 0.5 mm). Fine for cabinet layout and documentation; compare against the Phoenix Contact drawing before anything depends on exact positions.

At a glance

Input ranges
1 A / 5 A
AC, sine, 45 to 60 Hz
Output
0..10 V
or 0..20 mA, load < 750 ohm
Accuracy
< 0.5 %
of final value
Tempco
< 0.015 %/K
maximum
Step response
< 200 ms
10 to 90 %
Supply
loop-powered
no auxiliary supply

3D module datasheet-built, not manufacturer CAD

MCR-SLP-1-5-UI-0 3D model

Built from the manufacturer's dimension drawing and front view, with MCR-SLP-1-5-UI-0 laser-etched on the front. Open the 3D tab to spin it.

Specifications

Input 1 A0 to 1 A AC, overload 2 x IN (5 min at 60 C), surge 50 A (1 s), 1.6 VA
Input 5 A0 to 5 A AC, overload 2 x IN (5 min at 60 C), surge 100 A (1 s), 2.2 VA
Frequency50 Hz nominal, 45 to 60 Hz
Voltage output0 to 10 V, max. 20 V, load > 100 kohm, ripple < 50 mVpp
Current output0 to 20 mA, max. 30 mA, load < 750 ohm, ripple < 50 mVpp
Transmission error< 0.5 % of final value
Temperature coefficient< 0.015 %/K
Step response (10-90 %)< 200 ms
Test voltage3.5 kV; rated insulation 300 V AC to earth
Ambient temperature-25 to 60 C (storage -25 to 80 C)
ConnectionScrew, M3, 0.2 to 2.5 mm2 (24 to 14 AWG), strip 8 mm
HousingPolyamide PA, green, IP20
Dimensions22.5 W x 99 H x 114.5 D mm

Symbol & footprint

Schematic symbol by Adam Skotarczak
DIN-rail panel footprint (terminal positions approximate), front face on the TS35 rail

A cabinet panel-layout footprint, not a PCB land pattern: the outline is the 22.5 W x 99 H x 114.5 front face, the origin is the rail centre line, and the pads sit at the terminal positions so symbol pins and 3D terminals line up.

Pin map

The upstream symbol already uses Phoenix Contact's terminal numbers (1 to 4, 9 to 12); only its Footprint field was set.
Input, current4
11A1 A measuring input
25A5 A measuring input
3NCNot connected
41A/5ACommon return
Output4
9OUT ICurrent output 0 to 20 mA
10OUT UVoltage output 0 to 10 V
11GNDOutput ground
12GNDOutput ground

Order codes

Order no.ProductFeatures
2814359MCR-SLP-1-5-UI-0Passive current transducer 1/5 A AC to 0..10 V / 0..20 mA

Assets

KiCad symbolphoenix-mcr-slp-1-5-ui-0.kicad_sym (by Adam Skotarczak)
KiCad footprintPHOENIX_MCR-SLP-1-5-UI-0_DIN (DIN-rail panel footprint; terminal positions approximate)
3D model.step / .glb (datasheet-built, not manufacturer CAD; part number laser-etched)
Fusion 360 / EAGLEphoenix-mcr-slp-1-5-ui-0.lbr (generated by adom-lbr, passes adom-lbr validate, not import-tested in Fusion)
Canonicalphoenix-mcr-slp-1-5-ui-0.adom-lbr.json
KiCad PCMWhole library with this part: john/kicad-symlib (footprint library PCM_realAscot_DIN)
AltiumNot available yet. Open a pull request to add it.

Implementation

Datasheet

Download (PDF) · Phoenix Contact, MCR-SLP-1-5-UI-0 - 2814359, online catalog data sheet 10/29/2020 · www.phoenixcontact.com

Licence

Provenance